Liquid cooling system is managed by the controller module. It controls the working order of internal components and acceptable operating modes, gathers the data from the sensors installed inside the system and shows information on the built-in two-line display. The Controller Manual is applicable for controller firmware versions starting v.38.1.
Check the list of actual releases here
SENSOR NAME |
DESCRIPTION |
OPERATION LIMITS |
V | Cooling system power sensor | 10.8..13.2 V |
T0 | STM thermal sensor | -55º..+125ºC |
T1 | Coolant inlet temperature sensor | +3ºC..+60ºC |
T2 | Coolant outlet temperature sensor | +3ºC..+60ºC |
T3 | Air inlet temperature sensor | +3ºC..+35ºC |
T4 | Air outlet temperature sensor | +3ºC..+35ºC |
T5 | I2C thermal sensor placed on the controller board | -55º..+125ºC |
T6 | I2C thermal sensor for pumps and fans | -55º..+125ºC |
F1..F6 | Fans sensor | 300..3000 RPM |
P1..P2 | Pumps sensor | 1200..4600 RPM |
FLOW | Flow meter | |
RH | Humidity sensor placed on the controller board (starting Controller version 38.3) | 8%..90% |